Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*THIS APPLIES TO ALL UNITS THE "UFER" GROUND WAS INSTALLED CENTER OF THE SIDE SLIDING GLASS DOOR. NONE OF THE UNITS HAVE A "UFER" AT OR NEAR THE LOAD CENTER. WHAT REMEDY WILL BE TAKEN TO PROVIDE A MADE ELECTRODE UFER GROUND SOURCE FOR EACH OF THE ELEVEN (11) UNITS? REFER TO NEC ART 250 & CITY AMENDMENT. |
| 06/12/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*NOTES 1.) CABLE BUNDLED IN LENGTHS EXCEEDING 24" TO BE DE-RATED PER 310-15 NEC. |
| 06/07/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*SEE WRITE UP UNIT #2. |