Permit: T02CM00646

Parcel: 133233310


Addresses:

1066 N PRESSYC PL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/18/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*THIS APPLIES TO ALL UNITS THE "UFER" GROUND WAS INSTALLED CENTER OF THE SIDE SLIDING GLASS DOOR. NONE OF THE UNITS HAVE A "UFER" AT OR NEAR THE LOAD CENTER. WHAT REMEDY WILL BE TAKEN TO PROVIDE A MADE ELECTRODE UFER GROUND SOURCE FOR EACH OF THE ELEVEN (11) UNITS? REFER TO NEC ART 250 & CITY AMENDMENT.
06/12/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*NOTES 1.) CABLE BUNDLED IN LENGTHS EXCEEDING 24" TO BE DE-RATED PER 310-15 NEC.
06/07/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*SEE WRITE UP UNIT #2.