Permit Details

Status:
Closed
Type:
POOL - RESIDENTIAL
Address NEW:
2121 S PANTANO RD
Apply Date:
07/16/2002
Applicant:
JONATHAN BURNS
Description:
POOL:SPA
Contractors:
  • J 3 CONSTRUCTION L L C ,

Permit Reviews

Permit Number - T02BU01982
Permit Status: Closed
Permit Description: POOL:SPA
Start Date Submittal Complete Date Status  
07/16/2002 POOL/SPA 07/16/2002 COMPLETED Review Details

Outstanding Inspections

Permit Status: Closed
Permit Number: T02BU01982
Permite Description: POOL:SPA
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
POOL/SPA HEATER N/A Not Inspected
08/02/2002 POOL/SPA PLUMBING N/A Partial Approval IVRS - Inspection 0000*
08/02/2002 POOL/SPA ELECTRIC N/A Partial Approval IVRS - Inspection 0000*
08/02/2002 POOL/SPA GAS N/A Partial Approval IVRS - Inspection 0000*
12/06/2002 POOL/SPA FINAL/BARRIER N/A Denied IVRS - Inspection 0999*1.) SEAL CONDUIT WET NICHE FIXTURE
2.) AS WS PREVIOUSLY WRITTEN UP ON 10/14/2002 ENCAPSULATE GROUND CONNECTION WITH AN APPROVED COMPOUND (LEAVE ME THE CONTAINER SO I CAN VIERIFY PRODUCT & ITS LISTING. PER ROB FREDINGER.
3.) STRANDS CUT ON GROUNDING CONDUCTOR IS NOT AN ACCEPTED METHOD OF TERMINATING THE EQUIPMENT GROUNDING CONDUCTOR.
4.) A REINSPECTION IS REQ'D PRIOR TO THE WATER BEING PUT BACK IN SCHEDULE THROUGH STEVE LONG. 791-5550 1147 AFTER HTR. $102.

Completed Inspections

Permit Status: Closed
Permit Number: T02BU01982
Permit Description: POOL:SPA
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/02/2002 POOL/SPA PRE-GUNITE RSUBA Approved IVRS - Inspection 0000*