Inspection History Details
Inspection Status: Denied
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T02BU01982
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2002 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection 0999*1.) SEAL CONDUIT WET NICHE FIXTURE 2.) AS WS PREVIOUSLY WRITTEN UP ON 10/14/2002 ENCAPSULATE GROUND CONNECTION WITH AN APPROVED COMPOUND (LEAVE ME THE CONTAINER SO I CAN VIERIFY PRODUCT & ITS LISTING. PER ROB FREDINGER. 3.) STRANDS CUT ON GROUNDING CONDUCTOR IS NOT AN ACCEPTED METHOD OF TERMINATING THE EQUIPMENT GROUNDING CONDUCTOR. 4.) A REINSPECTION IS REQ'D PRIOR TO THE WATER BEING PUT BACK IN SCHEDULE THROUGH STEVE LONG. 791-5550 1147 AFTER HTR. $102. |
|
12/05/2002 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection 0999*BARRIER IS NOT ACCEPTABLE AT MASONRY/WROUGHT IRON JUNCTION CONNECTION. | |
10/21/2002 | POOL/SPA FINAL/BARRIER | Partial Approval | IVRS - Inspection 0000*FINISH DIRT WORK FILL NEEDED STILL BELOW FENCE. | |
10/14/2002 | POOL/SPA FINAL/BARRIER | Not ready for Inspection | IVRS - Inspection 0000*1) AT BOTTOM OF POOL FENCE, MAX SPACE IS 4" 2) GATE ON WEST SIDE NEED TOO BE ADJUSTED TO SELF CLOSE 3) LABEL PANEL 8 ALL CIRCUITS IN POOL PANEL, USE ITE BREAKERS 4) POOL BOILER IS 4000.000 BTU GAS SUPPLY COMES FROM BLDG GAS LINE WAS IT SEIZED FOR THIS BOILER? 5)INSIDE FIXTURE ( WET NICHE) GROUND CONNECTION TOO BE ENCAPSULATED WITH APPROVED COMPOUND NOT SILICONE!!! |