Permit: T01PL00717
Permit Details
Apply Date:
04/02/2001
Applicant:
ENGLE RICK
Description:
WATER HEATER:REPLACE T01VL00835
Permit Reviews
Permit Number - T01PL00717
Permit Status: Expired
Permit Description: WATER HEATER:REPLACE T01VL00835
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
04/02/2001 | PLUMBING | 04/02/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01PL00717
Permit Status: Expired
Permit Description: WATER HEATER:REPLACE T01VL00835
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
04/02/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01PL00717
Permite Description: WATER HEATER:REPLACE T01VL00835
Total Outstanding Inspections - 3
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2001 | PLUMBING - INTERMEDIATE | N/A | Denied | IVRS - Inspection 0999* |
04/13/2001 | PLUMBING - PROGRESS | N/A | Denied | IVRS - Inspection 0999* |
04/13/2001 | PLUMBING - FINAL | N/A | Denied | IVRS - Inspection 0999* 1) FLU VENT FOR WATER HEATER AND FURNACE MUST TERMINATE 1'-0" ABOVE COOLER WHEN FLU VENT IS LOCATED WITHIN 10' OF COOLER. 2) PA AND T DRAIN MUST NOT TURN DOWN ONTO ROOF. THIS DRAIN MUST SPRAY UP TO SKY FOR COOLING 3) FURNACE FLEX CONNECTOR CAN NOT GO THRU APPLIANCE HOUSING THIS MUST BE HARD PIPED THRU HOUSING THEN FLEX CONNECTOR 4) P AND T DRAIN HAS KINK IN LINE |