Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
12/13/2001
Applicant:
G T R HEATING AND AIR COND,*C
Description:
REPLACE:A/C & FURNACE(APA)
Contractors:
  • G T R HEATING AND AIR COND,*C

Outstanding Activity Conditions

Permit Number - T01ME01046
Permit Status: Expired
Permit Description: REPLACE:A/C & FURNACE(APA)
Total Outstanding Activity Conditions - 1
Date Name
12/13/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01ME01046
Permite Description: REPLACE:A/C & FURNACE(APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/08/2002 MECHANICAL - FINAL N/A Denied 1.) WATER LEAKING AT UNION & VALVE ON HUMIDIFIER WATER LINE. 2.) PROVIDE A TRAP ON CONDENSATE DRAIN LINE. 3.) #8 WIRE NOT ADEQUATE SIZE FOR 60 AMP CIRCUIT TO CONDENSOR FROM DISCONNECT. LOOSE WIRE INSIDE DISCONNECT. CORRECT & RECALL FOR INSPECTION.

Documents

File Name Document Type  
None DOCUMENTS VIEW