Permit: T01ME01046
Permit Details
Apply Date:
12/13/2001
Applicant:
G T R HEATING AND AIR COND,*C
Description:
REPLACE:A/C & FURNACE(APA)
Contractors:
- G T R HEATING AND AIR COND,*C
Outstanding Activity Conditions
Permit Number - T01ME01046
Permit Status: Expired
Permit Description: REPLACE:A/C & FURNACE(APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
12/13/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01ME01046
Permite Description: REPLACE:A/C & FURNACE(APA)
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2002 | MECHANICAL - FINAL | N/A | Denied | 1.) WATER LEAKING AT UNION & VALVE ON HUMIDIFIER WATER LINE. 2.) PROVIDE A TRAP ON CONDENSATE DRAIN LINE. 3.) #8 WIRE NOT ADEQUATE SIZE FOR 60 AMP CIRCUIT TO CONDENSOR FROM DISCONNECT. LOOSE WIRE INSIDE DISCONNECT. CORRECT & RECALL FOR INSPECTION. |