Permit: T01ME01046

Parcel: 136333050

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Permit Number - T01ME01046

Inspection Description - MECHANICAL - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
01/08/2002 MECHANICAL - FINAL Denied 1.) WATER LEAKING AT UNION & VALVE ON HUMIDIFIER WATER LINE. 2.) PROVIDE A TRAP ON CONDENSATE DRAIN LINE. 3.) #8 WIRE NOT ADEQUATE SIZE FOR 60 AMP CIRCUIT TO CONDENSOR FROM DISCONNECT. LOOSE WIRE INSIDE DISCONNECT. CORRECT & RECALL FOR INSPECTION.