Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T01ME01046
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2002 | MECHANICAL - FINAL | Denied | 1.) WATER LEAKING AT UNION & VALVE ON HUMIDIFIER WATER LINE. 2.) PROVIDE A TRAP ON CONDENSATE DRAIN LINE. 3.) #8 WIRE NOT ADEQUATE SIZE FOR 60 AMP CIRCUIT TO CONDENSOR FROM DISCONNECT. LOOSE WIRE INSIDE DISCONNECT. CORRECT & RECALL FOR INSPECTION. |