Permit: T01ME00912
Permit Details
Apply Date:
11/06/2001
Applicant:
AIR CONDITIONING BY ROBERTS ,
Description:
REPLACE:A/C UNIT
Contractors:
- AIR CONDITIONING BY ROBERTS ,
Permit Reviews
Permit Number - T01ME00912
Permit Status: Expired
Permit Description: REPLACE:A/C UNIT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/06/2001 | MECHANICAL | 11/06/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01ME00912
Permit Status: Expired
Permit Description: REPLACE:A/C UNIT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/06/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01ME00912
Permite Description: REPLACE:A/C UNIT
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2001 | MECHANICAL - FINAL | N/A | Denied | 1.) CONTROL WIRING CANNOT BE EXPOSED TO SUN/WEATHER. 2.) HI VOLTAGE FUSES MINIMUM 21.8 MAX 30. UNIT FUSED AT 15- 3.) CONDENSATE DRAIN CANNOT DUMP OFF EDGE OF ROOF. IMPROPER TERMINATION. 4.) SUPPLY/RETURN DUCT WORK AT UNIT ON ROOF. WHAT TYPE THICKNESS OF DUCT INTERINAL INSULATION USED. 5.) ELECTRIC DATA PLATE NOT COMPLETED |