Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/14/2001 |
MECHANICAL - FINAL |
|
Denied |
1.) CONTROL WIRING CANNOT BE EXPOSED TO SUN/WEATHER. 2.) HI VOLTAGE FUSES MINIMUM 21.8 MAX 30. UNIT FUSED AT 15- 3.) CONDENSATE DRAIN CANNOT DUMP OFF EDGE OF ROOF. IMPROPER TERMINATION. 4.) SUPPLY/RETURN DUCT WORK AT UNIT ON ROOF. WHAT TYPE THICKNESS OF DUCT INTERINAL INSULATION USED. 5.) ELECTRIC DATA PLATE NOT COMPLETED |