Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
6250 E 31ST ST
Address NEW:
6250 E 31ST ST
Apply Date:
06/27/2001
Applicant:
PARDO LAWRENCE ANTHONY
Description:
AIR COND REPLACEMENT T00VL01618

Permit Reviews

Permit Number - T01ME00547
Permit Status: Expired
Permit Description: AIR COND REPLACEMENT T00VL01618
Start Date Submittal Complete Date Status  
06/27/2001 MECHANICAL 06/27/2001 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01ME00547
Permit Status: Expired
Permit Description: AIR COND REPLACEMENT T00VL01618
Total Outstanding Activity Conditions - 1
Date Name
06/27/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01ME00547
Permite Description: AIR COND REPLACEMENT T00VL01618
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
07/02/2001 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*1.) DISCONNECT, FUSES, WIRE, ALL TOO SMALL SEE DATA PLATE FOR PROPER SIZING 2.) WHEN TERMINATING CONDERSATE OVER THE TOP OF A WASTE VENT USE A 3/4 TEL NOT AN ELBOW PAINT PVC W/LATER PAINT CORRECT & RECALL FOR FINAL INSPECTION.