Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) DISCONNECT, FUSES, WIRE, ALL TOO SMALL SEE DATA PLATE FOR PROPER SIZING 2.) WHEN TERMINATING CONDERSATE OVER THE TOP OF A WASTE VENT USE A 3/4 TEL NOT AN ELBOW PAINT PVC W/LATER PAINT CORRECT & RECALL FOR FINAL INSPECTION. |