Permit: T01ME00531
Permit Details
Apply Date:
06/20/2001
Applicant:
RUSSETT SERVICE CORPORATION, *C
Description:
REPLACE:A/C (APA)
Contractors:
- RUSSETT SERVICE CORPORATION, *C
Outstanding Activity Conditions
Permit Number - T01ME00531
Permit Status: Expired
Permit Description: REPLACE:A/C (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/20/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01ME00531
Permite Description: REPLACE:A/C (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2001 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999*1)CANN0T DRAIN CONDENSATE INTO A WASTE VENT SMALLER THAN 2".2)GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 90,000 BTU.SEE TABLE 3-D-2 1994 UMC FOR PROPER SIZING.CORRECT AND RECALL FOR FINAL INSPECTION. |