Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/22/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1)CANN0T DRAIN CONDENSATE INTO A WASTE VENT SMALLER THAN 2".2)GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 90,000 BTU.SEE TABLE 3-D-2 1994 UMC FOR PROPER SIZING.CORRECT AND RECALL FOR FINAL INSPECTION. |