Permit: T01ME00427
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
1871 N CAMINO ALICANTE
Address NEW:
1871 N CAMINO ALICANTE
Apply Date:
05/15/2001
Applicant:
BOSS CONSTRUCTION INC. *T
Description:
INSTALL:HEAT PUMP (APA)
Contractors:
- BOSS CONSTRUCTION INC. *T
Outstanding Activity Conditions
Permit Number - T01ME00427
Permit Status: Expired
Permit Description: INSTALL:HEAT PUMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/15/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01ME00427
Permite Description: INSTALL:HEAT PUMP (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2001 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999*1)PROVIDE ADEQUATE CLEARANCE TO SERVICE ACCESS PANELS ON SOUTH END OF UNIT.SEE INSTALLATION INSTRUCTIONS FOR PROPER CLEARANCE.2)REPAIR BROKEN SUPPLY DUCT ON ROOF.3)MARK DATA PLATE WITH PROPPER HEAT STRIP AND FUSE UNIT ACCORDINGLY.4)BLOCK ELECT. CONDUIT.5)PAINT EXPOSED PVC WITH LATEX PAINT, DON'T SPRAY ENAMAL.6)BLOCK AND CLAMP PVC EVERY 4'.7)REPAIR ELECT. DISCONNECT SO THAT DOOR WILL SHUT.8)CONSENSATE CANNOT DRAIN INTO A WASTE VENT SMALLER THAN 2". CORRECT AND RECALL FOR FINAL INSPECTION. |