Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
1871 N CAMINO ALICANTE
Apply Date:
05/15/2001
Applicant:
BOSS CONSTRUCTION INC. *T
Description:
INSTALL:HEAT PUMP (APA)
Contractors:
  • BOSS CONSTRUCTION INC. *T

Outstanding Activity Conditions

Permit Number - T01ME00427
Permit Status: Expired
Permit Description: INSTALL:HEAT PUMP (APA)
Total Outstanding Activity Conditions - 1
Date Name
05/15/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01ME00427
Permite Description: INSTALL:HEAT PUMP (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
06/12/2001 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*1)PROVIDE ADEQUATE CLEARANCE TO SERVICE ACCESS PANELS ON SOUTH END OF UNIT.SEE INSTALLATION INSTRUCTIONS FOR PROPER CLEARANCE.2)REPAIR BROKEN SUPPLY DUCT ON ROOF.3)MARK DATA PLATE WITH PROPPER HEAT STRIP AND FUSE UNIT ACCORDINGLY.4)BLOCK ELECT. CONDUIT.5)PAINT EXPOSED PVC WITH LATEX PAINT, DON'T SPRAY ENAMAL.6)BLOCK AND CLAMP PVC EVERY 4'.7)REPAIR ELECT. DISCONNECT SO THAT DOOR WILL SHUT.8)CONSENSATE CANNOT DRAIN INTO A WASTE VENT SMALLER THAN 2".
CORRECT AND RECALL FOR FINAL INSPECTION.