Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1)PROVIDE ADEQUATE CLEARANCE TO SERVICE ACCESS PANELS ON SOUTH END OF UNIT.SEE INSTALLATION INSTRUCTIONS FOR PROPER CLEARANCE.2)REPAIR BROKEN SUPPLY DUCT ON ROOF.3)MARK DATA PLATE WITH PROPPER HEAT STRIP AND FUSE UNIT ACCORDINGLY.4)BLOCK ELECT. CONDUIT.5)PAINT EXPOSED PVC WITH LATEX PAINT, DON'T SPRAY ENAMAL.6)BLOCK AND CLAMP PVC EVERY 4'.7)REPAIR ELECT. DISCONNECT SO THAT DOOR WILL SHUT.8)CONSENSATE CANNOT DRAIN INTO A WASTE VENT SMALLER THAN 2". CORRECT AND RECALL FOR FINAL INSPECTION. |