Permit: T01ME00272
Permit Details
Apply Date:
03/30/2001
Applicant:
KELLY AIR CONDITIONING , *C
Description:
INSTALL:5 TON GAS PACK (APA)
Contractors:
- KELLY AIR CONDITIONING , *C
Outstanding Activity Conditions
Permit Number - T01ME00272
Permit Status: Expired
Permit Description: INSTALL:5 TON GAS PACK (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
03/30/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01ME00272
Permite Description: INSTALL:5 TON GAS PACK (APA)
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2001 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999* 1) GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 96,000 BTU. SEE TABLE 3-D-2 1994 UMC FOR PROPER SIZING 2) A/C UNIT MUST SIT ENTIRELY ON BASE. 3) PROVIDE WEATHER PROTECTION OVER FLEX DUCTS. |