Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T01ME00272
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1) GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 96,000 BTU. SEE TABLE 3-D-2 1994 UMC FOR PROPER SIZING 2) A/C UNIT MUST SIT ENTIRELY ON BASE. 3) PROVIDE WEATHER PROTECTION OVER FLEX DUCTS. |