Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/02/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 96,000 BTU. SEE TABLE 3-D-2 1994 UMC FOR PROPER SIZING 2) A/C UNIT MUST SIT ENTIRELY ON BASE. 3) PROVIDE WEATHER PROTECTION OVER FLEX DUCTS. |