Permit: T01EL02681
Permit Details
Apply Date:
11/05/2001
Applicant:
EARLINE DOWNEY
Description:
UPGRADE:ELECTRIC TO 200 AMP
Permit Reviews
Permit Number - T01EL02681
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
11/05/2001 | ELECTRICAL | 11/05/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01EL02681
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
11/05/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T01EL02681
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Total Completed Inspections - 4
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/31/2001 | ELECTRIC - FINAL | MCAPISTR | Approved | IVRS - Inspection 0210* |
12/31/2001 | ELECTRIC - SERVICE UPGRADE | MCAPISTR | Approved | IVRS - Inspection 0215* |
12/31/2001 | ELECTRIC - CABLE DROP | MCAPISTR | Approved | IVRS - Inspection 0215*1.) SERVICE ENTRANCE CONDUCTORS MUST BE EITHER 2/0 COPPER OR 4/0 ALUMINUM. 2.) THE GROUNDING IS INCORRECT. THE COLD WATER. PIPING AND THE GAS LINE MUST BE BONDED TO THE GROUND RODS OR SERVICE PANEL. 3.) THE ADDITIONS TO THE HOUSE MUST BE SET TO PLANS AND SUBMITTED TO THE CITY DEVELOPEMENT SERVICES DEPT. FOR APPROVAL AND PERMIT. |
08/15/2002 | PERMIT FINALED | MCAPISTR | Approved |