Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01EL02681
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
01/11/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*PERMITS FOR 1.) BUILDING, 2.) PLUMBING & ELECTRICAL CIRCUIT, AND MECHANCIAL WORK MUST BE SECURED. | |
12/31/2001 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0215*1.) SERVICE ENTRANCE CONDUCTORS MUST BE EITHER 2/0 COPPER OR 4/0 ALUMINUM. 2.) THE GROUNDING IS INCORRECT. THE COLD WATER. PIPING AND THE GAS LINE MUST BE BONDED TO THE GROUND RODS OR SERVICE PANEL. 3.) THE ADDITIONS TO THE HOUSE MUST BE SET TO PLANS AND SUBMITTED TO THE CITY DEVELOPEMENT SERVICES DEPT. FOR APPROVAL AND PERMIT. |