Permit: T01EL02681

Parcel: 130070120


Addresses:

3738 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01EL02681

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
01/11/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*PERMITS FOR 1.) BUILDING, 2.) PLUMBING & ELECTRICAL CIRCUIT, AND MECHANCIAL WORK MUST BE SECURED.
12/31/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*1.) SERVICE ENTRANCE CONDUCTORS MUST BE EITHER 2/0 COPPER OR 4/0 ALUMINUM. 2.) THE GROUNDING IS INCORRECT. THE COLD WATER. PIPING AND THE GAS LINE MUST BE BONDED TO THE GROUND RODS OR SERVICE PANEL. 3.) THE ADDITIONS TO THE HOUSE MUST BE SET TO PLANS AND SUBMITTED TO THE CITY DEVELOPEMENT SERVICES DEPT. FOR APPROVAL AND PERMIT.