Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
10/31/2001
Applicant:
SOUTHWEST ENERGY SOLUTIONS INC ,
Description:
UPGRADE:ELECTRIC TO 200 AMP (APA)
Contractors:
  • SOUTHWEST ENERGY SOLUTIONS INC ,

Outstanding Activity Conditions

Permit Number - T01EL02659
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC TO 200 AMP (APA)
Total Outstanding Activity Conditions - 1
Date Name
10/31/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01EL02659
Permite Description: UPGRADE:ELECTRIC TO 200 AMP (APA)
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
ELECTRIC - FINAL N/A Not Inspected
11/19/2001 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection 0220*BE ADVISED: N.E.C ART 250 ALLOWS THE GROUNDING CONDUCTOR TOBE SPLICE ONLY WITH IRREVESBILE METHODS SUCH AS CRIMP TERMINATIONS OR EXOTHERMIC WELDING (CADWELD). THE SPLIT BOLT KEARNEY IS NOT ACCEPTIBLE CORRECT & RECALL THANKS.