Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T01EL02659
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0220*BE ADVISED: N.E.C ART 250 ALLOWS THE GROUNDING CONDUCTOR TOBE SPLICE ONLY WITH IRREVESBILE METHODS SUCH AS CRIMP TERMINATIONS OR EXOTHERMIC WELDING (CADWELD). THE SPLIT BOLT KEARNEY IS NOT ACCEPTIBLE CORRECT & RECALL THANKS. |