Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
219 W KENTUCKY ST
Apply Date:
10/31/2001
Applicant:
SEVERO MARTINEZ
Description:
UPGRADE:ELECTRIC 100 AMP TO 200 AMP

Permit Reviews

Permit Number - T01EL02657
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100 AMP TO 200 AMP
Start Date Submittal Complete Date Status  
10/31/2001 ELECTRICAL 10/31/2001 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01EL02657
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100 AMP TO 200 AMP
Total Outstanding Activity Conditions - 1
Date Name
10/31/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01EL02657
Permite Description: UPGRADE:ELECTRIC 100 AMP TO 200 AMP
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
ELECTRIC - FINAL N/A Not Inspected
11/01/2001 ELECTRIC - CABLE DROP N/A Denied SERVICE 1. BOARD BEHIND SERVICE TO BE PAINTED 2.) NEED WATER & GAS BOND 3.) RISER TO HAVE 2 SUPPORTS BELOW ROOF USE NEW SUPPORT ALSO INSTALL A GUY BACK SUPPORT SINCE RISER 3 ABOVE ROOF. 4.) ADDRESS SERVICE. HOUSE HAS HAD REWIRING DONE TO ALL INSIDE CHECKED WITH OFFICE, THERE IS NO RECORD OF PERMIT OR INSPECTION. YOU WILL HAVE TO OBTAIN A PERMIT FOR WIRING INSIDE AND PROVIDE A PLAN TO DEVELOPMENT SERVICE GET APPROVED AND RECALL INSPECTION. HAVE YOUR ELECTRICIAN DRAW UP PLAN AND SUBMIT.
11/02/2001 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection 0999*