Permit: T01EL02657

Parcel: 120086300


Addresses:

219 W KENTUCKY ST


Inspection Status: Denied

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01EL02657

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Denied

Date Description Inspector Results Comments
11/01/2001 ELECTRIC - CABLE DROP Denied SERVICE 1. BOARD BEHIND SERVICE TO BE PAINTED 2.) NEED WATER & GAS BOND 3.) RISER TO HAVE 2 SUPPORTS BELOW ROOF USE NEW SUPPORT ALSO INSTALL A GUY BACK SUPPORT SINCE RISER 3 ABOVE ROOF. 4.) ADDRESS SERVICE. HOUSE HAS HAD REWIRING DONE TO ALL INSIDE CHECKED WITH OFFICE, THERE IS NO RECORD OF PERMIT OR INSPECTION. YOU WILL HAVE TO OBTAIN A PERMIT FOR WIRING INSIDE AND PROVIDE A PLAN TO DEVELOPMENT SERVICE GET APPROVED AND RECALL INSPECTION. HAVE YOUR ELECTRICIAN DRAW UP PLAN AND SUBMIT.