Permit: T01EL02443
Permit Details
Apply Date:
10/02/2001
Applicant:
KELLY MARY
Description:
REPLACE:ELECTRIC METER
Contractors:
- 2 EAGLE ELECTRIC ,
Permit Reviews
Permit Number - T01EL02443
Permit Status: Expired
Permit Description: REPLACE:ELECTRIC METER
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/02/2001 | ELECTRICAL | 10/02/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01EL02443
Permit Status: Expired
Permit Description: REPLACE:ELECTRIC METER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/02/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01EL02443
Permite Description: REPLACE:ELECTRIC METER
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected | ||
| 10/03/2001 | ELECTRIC - SERVICE RELOCATION | N/A | Not ready for Inspection | 1.) PUT A PRMANENT ADDRESS ON SERVICE 2.) 2 GROUND RODS REQUIRED 3.) CODE REQUIRES A WATER BOND AND GAS BOND. 4.) USE ROOF JACK ABOVE ROOF 5.) USE 1/4" HARDWARE TO STAP RISER-USE 2 STRAPS BELOW ROOF. 6.) STRAP GROUND WIRE TO STRUCTURE. CALL TEP TO DISCONNECT OLD SERVICE AND RUN CIRCUITS FROM NEW SERVICE TO OLD TIE-IN AND INSTALL CIRCUIT BREAKERS. |
| 10/15/2001 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection 0000*APPROVAL PARTIAL OK TO CLEAR SERVICE INCREASE. CALL BACK WHEN CHANGE OVER COMPLETE 1.) INSTALL SPLICE IN PORCH IN A BOX. 2.) MAKE A COVER FOR INSIDE FUSE BOX TO COVER ALL OPENINGS 3.) REPLACE WIRING TO KITCHEN LIGHT. 4.) INSTALL SMOKE DETECTOR. 5.) REPLACE WIRING ABOVE PORCH TO COOLER. |