Permit: T01EL02443

Parcel: 138111530


Addresses:

6364 S DUNTON AV

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
10/03/2001 ELECTRIC - SERVICE RELOCATION Not ready for Inspection 1.) PUT A PRMANENT ADDRESS ON SERVICE 2.) 2 GROUND RODS REQUIRED 3.) CODE REQUIRES A WATER BOND AND GAS BOND. 4.) USE ROOF JACK ABOVE ROOF 5.) USE 1/4" HARDWARE TO STAP RISER-USE 2 STRAPS BELOW ROOF. 6.) STRAP GROUND WIRE TO STRUCTURE. CALL TEP TO DISCONNECT OLD SERVICE AND RUN CIRCUITS FROM NEW SERVICE TO OLD TIE-IN AND INSTALL CIRCUIT BREAKERS.