Permit: T01EL02404
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2501 N COLUMBUS BL
Address NEW:
2501 N COLUMBUS BL
Apply Date:
09/26/2001
Applicant:
RICHARD CZECH
Description:
SERVICE:ELECTRIC
Permit Reviews
Permit Number - T01EL02404
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/26/2001 | ELECTRICAL | 09/26/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01EL02404
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/26/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01EL02404
Permite Description: SERVICE:ELECTRIC
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - CABLE DROP | N/A | Not Inspected | ||
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected | ||
| 10/05/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999*DENIED. THE RATING OF THE NEW SERVICE CAPCITY WILL BE 100 AMPS, THE METER ENCLOSURE IS NOT RATED FOR 100AMPS. YOU ARE REQUIRED TO INSTALL A METER ENCLOSURE RATED FOR 100 AMPS. SINCE THIS IS AN UPRANGE OLD GROUNDING NO LONGER APPROVED FOR UPGRADE. WILL HAVE TO COMPLY WITH CURRENT 99 NEC STANDARDS. THIS HOUSE APPEARS TO BE UN-OCCUPPIED, THUR THE STATE REGISTAR OF CONTRACTORS REQUIRES THIS WORK TO BE DONE BY A C-11 ELECTRICAL CONTRACTOR. |