Permit: T01EL02404

Parcel: 110073740


Addresses:

2501 N COLUMBUS BL

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/05/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*DENIED. THE RATING OF THE NEW SERVICE CAPCITY WILL BE 100 AMPS, THE METER ENCLOSURE IS NOT RATED FOR 100AMPS. YOU ARE REQUIRED TO INSTALL A METER ENCLOSURE RATED FOR 100 AMPS. SINCE THIS IS AN UPRANGE OLD GROUNDING NO LONGER APPROVED FOR UPGRADE. WILL HAVE TO COMPLY WITH CURRENT 99 NEC STANDARDS. THIS HOUSE APPEARS TO BE UN-OCCUPPIED, THUR THE STATE REGISTAR OF CONTRACTORS REQUIRES THIS WORK TO BE DONE BY A C-11 ELECTRICAL CONTRACTOR.
09/27/2001 ELECTRIC - FINAL Denied NOTES 1.) DOUBLE LUGGING IN DISCONNECT SWITCH NOT ALLOWED. 2.) NOT BONDED TO ENCLOSURE GROUNDING ELECTRODE CONDUCTOR 3.) USE PROPER WIRING METHODS PER ART 230 N.E.C. 4.)MIN SERVICE UPGRADE TO BE 100 AMPS PER N.E.C.