Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
DUPLEX OTHER
Address NEW:
2726 N COLUMBUS BL #01
Apply Date:
09/05/2001
Applicant:
IRONWOOD ELECTRIC ''T''
Description:
ELECTRIC:UPGRADE 100-200AMPS(APA)
Contractors:
  • IRONWOOD ELECTRIC ''T''

Outstanding Activity Conditions

Permit Number - T01EL02255
Permit Status: Expired
Permit Description: ELECTRIC:UPGRADE 100-200AMPS(APA)
Total Outstanding Activity Conditions - 1
Date Name
09/05/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01EL02255
Permite Description: ELECTRIC:UPGRADE 100-200AMPS(APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
09/07/2001 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0245*NOTES 1.) PROVIDE ADDITIONAL CORROSION PROTECTION FOR EMT CONDUIT STUBBED INTO EARTH. 2.) PROVIDE BUSHED ENDS WHERE FEEDERS ENTER OR EXIT CONDUIT. 3.) PROVIDE EQUIP. GROUND AND ISOLATE NEUTRAL BAR FROM GROUND BAR. 4.) COLOR CODE WIRING CORRECTLY. 5.) BOND WATER & GAS PIPING.