Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/07/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) PROVIDE ADDITIONAL CORROSION PROTECTION FOR EMT CONDUIT STUBBED INTO EARTH. 2.) PROVIDE BUSHED ENDS WHERE FEEDERS ENTER OR EXIT CONDUIT. 3.) PROVIDE EQUIP. GROUND AND ISOLATE NEUTRAL BAR FROM GROUND BAR. 4.) COLOR CODE WIRING CORRECTLY. 5.) BOND WATER & GAS PIPING. |