Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL02255

Parcel: 110080460

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/07/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) PROVIDE ADDITIONAL CORROSION PROTECTION FOR EMT CONDUIT STUBBED INTO EARTH. 2.) PROVIDE BUSHED ENDS WHERE FEEDERS ENTER OR EXIT CONDUIT. 3.) PROVIDE EQUIP. GROUND AND ISOLATE NEUTRAL BAR FROM GROUND BAR. 4.) COLOR CODE WIRING CORRECTLY. 5.) BOND WATER & GAS PIPING.