Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
922 W ACADIA DR
Address NEW:
922 W ACADIA DR
Apply Date:
08/31/2001
Applicant:
QUIJADA MARISELDA
Description:
RECONNECT:ELECTRIC:SFR

Outstanding Activity Conditions

Permit Number - T01EL02236
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC:SFR
Total Outstanding Activity Conditions - 1
Date Name
08/31/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01EL02236
Permite Description: RECONNECT:ELECTRIC:SFR
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
09/19/2001 ELECTRIC - FINAL N/A Denied THE FOLLOWING WILL REQUIRE CORRECTION AND FURTHER INSPECTION. FAILURE TO COMPLY WILL RESULT IN ELECTRIC SERVICE BEING DISCONTINUED 1.) THE GUEST HOUSE MUST HAVE ITS OWN ELECTRICAL LOAD CENTER/PANEL LOCATED INSIDE OF THE UNIT. 2.) THE UNDERGROUND CONDUIT FROM THE MAIN SERVICE PANEL TO HOUSE MUST BE SIZED TO THE NEW LOAD CONDUCTORS TO SERVE THE QUEST HOUSE. 3.) FOR THE PRESENT TIME CHANGE THE 20AMP CIRCUIT BREAKERS TO 15 AMP BECAUSE THE WIRES SERVING THE GUEST HOUSE ARE 14 GAUGE AND ARE RATED TO CARRY NO MORE THAN 15 AMPS...

Completed Inspections

Permit Status: Expired
Permit Number: T01EL02236
Permit Description: RECONNECT:ELECTRIC:SFR
Total Completed Inspections - 1
Date Description Inspector Results Comments
09/17/2001 ELECTRIC - RECONNECT MCAPISTR Approved IVRS - Inspection 0000*CHECK THAT YOU HAVE THE FOLLOWING 2.) SMOKE DETECTORS IN A HALL NEAR BEDROOMS 3.) ALL PLUGS AND SWITCHES WITH COVERS 4.) NO EXPOSED WIRING ( IN HEATER CLOSET AND ELSE WHERE). 5.) NO BARE BULBS OR FIXTURES WITHOUT BULB COVER IN CLOSETS.