Permit: T01EL02236

Parcel: 138233290


Addresses:

922 W ACADIA DR

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/19/2001 ELECTRIC - FINAL Denied THE FOLLOWING WILL REQUIRE CORRECTION AND FURTHER INSPECTION. FAILURE TO COMPLY WILL RESULT IN ELECTRIC SERVICE BEING DISCONTINUED 1.) THE GUEST HOUSE MUST HAVE ITS OWN ELECTRICAL LOAD CENTER/PANEL LOCATED INSIDE OF THE UNIT. 2.) THE UNDERGROUND CONDUIT FROM THE MAIN SERVICE PANEL TO HOUSE MUST BE SIZED TO THE NEW LOAD CONDUCTORS TO SERVE THE QUEST HOUSE. 3.) FOR THE PRESENT TIME CHANGE THE 20AMP CIRCUIT BREAKERS TO 15 AMP BECAUSE THE WIRES SERVING THE GUEST HOUSE ARE 14 GAUGE AND ARE RATED TO CARRY NO MORE THAN 15 AMPS...
09/17/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
09/14/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0925*
09/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
09/04/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0920*1.) THE HOUSE MUST BE OPEN SO AN INSPECTION OF THE INTERIOR CAN BE DONE. 2.) THE SECOND 2ND HOUSE LOCATED AT THE REAR OF THE LOT MUST ALSO BE LEFT UNLOCKED. 3.) PROVIDE PROOF COPY OF PERMIT AND BUILDING PLANS.) THAT THE SECOND HOUSE AND THE CARPORT, ATTACHED TO THE FRONT HOUSE AT REAR LEFT SIDE, WERE CONSTRUCTED UNDER A VALID CITY OF TUCSON BUILDING PERMIT. 4.) THE CARPORT WAS CONSTRUCTED WITH MANY VIOLATIONS OF THE BUILDING CODE.