Permit: T01EL02215
Permit Details
Apply Date:
08/28/2001
Applicant:
SMITH LUCY CRANWELL
Description:
SERVICE:ELECTRIC UNDERGROUND
Permit Reviews
Permit Number - T01EL02215
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC UNDERGROUND
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/28/2001 | ELECTRICAL | 08/28/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01EL02215
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC UNDERGROUND
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/28/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01EL02215
Permite Description: SERVICE:ELECTRIC UNDERGROUND
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2002 | ELECTRIC - FINAL | N/A | Not ready for Inspection | IVRS - Inspection 0000* |
Completed Inspections
Permit Status: Expired
Permit Number: T01EL02215
Permit Description: SERVICE:ELECTRIC UNDERGROUND
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2002 | ELECTRIC - TEMPORARY SERVICE | DSANTACR | Approved | IVRS - Inspection 0000* |
| 01/31/2002 | ELECTRIC - CABLE DROP | DSANTACR | Approved | IVRS - Inspection 0000*NOTES 1.) INSTALL BOND BUSHING ON 1 1/4" CONDUIT CONNECTOR AT CONCENTRIC KO. 250-96 NEC. 2.)INSTALL CONNECTORS WITH BUSHED ENDS WHERE DIRECT BURIAL CONDUCTORS EXIT CONDUIT TO PROTECT CABLES FROM ABRASION, NEC. 300-15 C - 300-16. 3.) NEED TO VERIFY GAS PIPE BONDING. |