Permit: T01EL02215

Parcel: 123060800


Addresses:

2028 E LEE ST

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
01/31/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*NOTES 1.) INSTALL BOND BUSHING ON 1 1/4" CONDUIT CONNECTOR AT CONCENTRIC KO. 250-96 NEC. 2.)INSTALL CONNECTORS WITH BUSHED ENDS WHERE DIRECT BURIAL CONDUCTORS EXIT CONDUIT TO PROTECT CABLES FROM ABRASION, NEC. 300-15 C - 300-16. 3.) NEED TO VERIFY GAS PIPE BONDING.