Permit: T01EL02137
Permit Details
Apply Date:
08/17/2001
Applicant:
GOODMAN GREG
Description:
RECONNECT:ELECTRIC:OFFICE
Outstanding Activity Conditions
Permit Number - T01EL02137
Permit Status: Withdrwn
Permit Description: RECONNECT:ELECTRIC:OFFICE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/17/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Withdrwn
Permit Number: T01EL02137
Permite Description: RECONNECT:ELECTRIC:OFFICE
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2001 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection 0999*1.) SECURE PANEL COVER TO PANEL AND PANEL TO WALL 2.) NEED SEALING DEVICES ON PANEL ABOVE BUSS. 3.) LOOSE FITTINGS AND IMPROPER SIZED FITTINGS 4.) USE APPROVED FITTING FOR M/C CABLE 5.) PROVIDE GROUNDING ELECTROBE SYSTEM. 6.) USE APPROVED FITTING TO CONNECT CONDUIT TO BOXES 7.) SUPPORT CONDUIT AS PER CODE. 8.) NEED TO OBTAIN GENERAL RE PAIR PERMIT FOR INTERIOR ELECTRICAL WORK. PROVIDE PLANS WITH FLOOR PLAN ELECTRICAL LAYOUT AND LOAD CALCULATIONS.9.) VERIFY LICENSED ELECTRICAL CONTRACTOR BEFORE PROCEEDING WITH FUTHER WORK *CHECK ROOF NEXT VISIT. |
08/20/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999* |