Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
Permit Number - T01EL02137
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*1.) SECURE PANEL COVER TO PANEL AND PANEL TO WALL 2.) NEED SEALING DEVICES ON PANEL ABOVE BUSS. 3.) LOOSE FITTINGS AND IMPROPER SIZED FITTINGS 4.) USE APPROVED FITTING FOR M/C CABLE 5.) PROVIDE GROUNDING ELECTROBE SYSTEM. 6.) USE APPROVED FITTING TO CONNECT CONDUIT TO BOXES 7.) SUPPORT CONDUIT AS PER CODE. 8.) NEED TO OBTAIN GENERAL RE PAIR PERMIT FOR INTERIOR ELECTRICAL WORK. PROVIDE PLANS WITH FLOOR PLAN ELECTRICAL LAYOUT AND LOAD CALCULATIONS.9.) VERIFY LICENSED ELECTRICAL CONTRACTOR BEFORE PROCEEDING WITH FUTHER WORK *CHECK ROOF NEXT VISIT. |