Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T01EL01569
Permit Details
Apply Date:
06/15/2001
Applicant:
PRESIDIO ELECTRIC SERVICES INC,*C
Description:
ELEC:SERVICE UPGRADE FROM 60 TO 125 (APA)
Contractors:
- PRESIDIO ELECTRIC SERVICES INC,*C
Outstanding Activity Conditions
Permit Number - T01EL01569
Permit Status: Expired
Permit Description: ELEC:SERVICE UPGRADE FROM 60 TO 125 (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/15/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01EL01569
Permite Description: ELEC:SERVICE UPGRADE FROM 60 TO 125 (APA)
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999*1.) IDENTIFY NEUTRAL AT WEATHER HEAD. 2.) LOOSE FITTINGS 3.) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 4.) NOT ENOUGH BREAKER SPACES FOR THE NUMBER OF UNGROUNDED CONDUCTORS IN PANEL. 5.) NEED TO HAVE ELECTRICIAN PRESENT TO REMOVE METER TO VERIFY BONDING OF SERVICE NIPPLE. 6.) STRAP CONDUIT AS PER CODE 3" WITHIN FITTINGS. |