Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL01569
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) IDENTIFY NEUTRAL AT WEATHER HEAD. 2.) LOOSE FITTINGS 3.) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 4.) NOT ENOUGH BREAKER SPACES FOR THE NUMBER OF UNGROUNDED CONDUCTORS IN PANEL. 5.) NEED TO HAVE ELECTRICIAN PRESENT TO REMOVE METER TO VERIFY BONDING OF SERVICE NIPPLE. 6.) STRAP CONDUIT AS PER CODE 3" WITHIN FITTINGS. |