Permit: T01EL01376
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
1011 W COLORADO ST #01
Address NEW:
1011 W COLORADO ST #01
Apply Date:
06/01/2001
Applicant:
WEST AJO CONTRACTING INC ,
Description:
ELECTRIC:UPGRADE 200AMPS
Contractors:
- WEST AJO CONTRACTING INC ,
Outstanding Activity Conditions
Permit Number - T01EL01376
Permit Status: Final
Permit Description: ELECTRIC:UPGRADE 200AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/01/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T01EL01376
Permit Description: ELECTRIC:UPGRADE 200AMPS
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2001 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection 0000* |
| 06/04/2001 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection 0999*1)NEED PERMANENT ADDRESSES ON SERVICE-MAKER NO GOOD.2)#4 GROUND NEEDS TO TIE TO NEUTRAL OR INSTALL A MAIN BONDING JUMPER TO NEUTRAL FROM GROUND BAR(#4).3)SUPPORT 1 1/2" PVC SCH 80' WITH IN 3' OF SERVICE.4)FRONT HOUSE SERVICE NOW NEEDS ITS OWN GROUND SYSTEM 2 GROUND RODS, WATER AND GAS BONDS 99 NEC 250-26.5)FRONT HOUSE-CORRECT WIRING ON LIGHT FIXTURE ABOVE SERVICE AND MARK SISCON "FRONT".6)MH SERVICE NOT READY.7)PROVIDE NAME OF C-11-LEAVE ON MESSAGE AT NEXT REQUEST. |
| 06/05/2001 | PERMIT FINALED | LHANLY | Approved | |
| 06/05/2001 | ELECTRIC - SERVICE UPGRADE | LHANLY | Approved | IVRS - Inspection 0000* |
| 06/05/2001 | ELECTRIC - CABLE DROP | LHANLY | Approved | IVRS - Inspection 0000* |