Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1)NEED PERMANENT ADDRESSES ON SERVICE-MAKER NO GOOD.2)#4 GROUND NEEDS TO TIE TO NEUTRAL OR INSTALL A MAIN BONDING JUMPER TO NEUTRAL FROM GROUND BAR(#4).3)SUPPORT 1 1/2" PVC SCH 80' WITH IN 3' OF SERVICE.4)FRONT HOUSE SERVICE NOW NEEDS ITS OWN GROUND SYSTEM 2 GROUND RODS, WATER AND GAS BONDS 99 NEC 250-26.5)FRONT HOUSE-CORRECT WIRING ON LIGHT FIXTURE ABOVE SERVICE AND MARK SISCON "FRONT".6)MH SERVICE NOT READY.7)PROVIDE NAME OF C-11-LEAVE ON MESSAGE AT NEXT REQUEST. |
|
| 06/04/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* |