Permit: T01EL01376

Parcel: 116172660

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/04/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1)NEED PERMANENT ADDRESSES ON SERVICE-MAKER NO GOOD.2)#4 GROUND NEEDS TO TIE TO NEUTRAL OR INSTALL A MAIN BONDING JUMPER TO NEUTRAL FROM GROUND
BAR(#4).3)SUPPORT 1 1/2" PVC SCH 80' WITH IN 3' OF SERVICE.4)FRONT HOUSE SERVICE NOW NEEDS ITS OWN GROUND SYSTEM 2 GROUND RODS, WATER AND GAS BONDS 99 NEC 250-26.5)FRONT HOUSE-CORRECT WIRING ON LIGHT FIXTURE ABOVE
SERVICE AND MARK SISCON "FRONT".6)MH SERVICE NOT READY.7)PROVIDE NAME OF C-11-LEAVE ON MESSAGE AT NEXT REQUEST.
06/04/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*