Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
1021 E 27TH ST
Address NEW:
1021 E 27TH ST
Apply Date:
05/01/2001
Applicant:
R H BENSON
Description:
INSTALL:ELECTRIC PEDESTAL:MH

Permit Reviews

Permit Number - T01EL01045
Permit Status: Expired
Permit Description: INSTALL:ELECTRIC PEDESTAL:MH
Start Date Submittal Complete Date Status  
05/01/2001 ELECTRICAL 05/01/2001 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01EL01045
Permit Status: Expired
Permit Description: INSTALL:ELECTRIC PEDESTAL:MH
Total Outstanding Activity Conditions - 1
Date Name
05/01/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01EL01045
Permite Description: INSTALL:ELECTRIC PEDESTAL:MH
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
07/17/2001 ELECTRIC - CABLE DROP N/A Denied IVRS - Inspection 0999*1.) 4 X 4 POLE DOES NOT MEET TEP REQUIREMENTS OF 17" MINIMUM CIRCUMERENCE AT POWER POLE. 2.) POLE TO BE MINIMUM OF 12" ABOVE WEATHER HEAD 3.) METER SOCKET TO BE MAXIMUM 6' 3" TO CENTERLINE ABOVE GRADE. 4.) METER BOARD TO BE TREATED FOR OUTDOOR APPLICATION AND MINMUM OF 3/4" THICK 5.) GROUND ROD SHOULD BE MINIMUM 6" APART 6.) METER BOARD TO BE SECURELY FASTERED TO POLE 7.) VERIFY POLE IS SET DEEP 8.) SCHEDULE 80 FROM SERVICE NEEDS TO BE SECURED 9.) 3' OF WORKING CLEARANE NECESSARY IN FRONT OF SERVICE 10.) DISCONNECT FOR MOBILE HOME REQUIRED WITHIN 30' OF HOME.
07/17/2001 ELECTRIC - TEMPORARY SERVICE N/A Denied IVRS - Inspection 0999*1
07/17/2001 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0999*

Documents

File Name Document Type  