Inspection Status: Denied
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 07/17/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*1.) 4 X 4 POLE DOES NOT MEET TEP REQUIREMENTS OF 17" MINIMUM CIRCUMERENCE AT POWER POLE. 2.) POLE TO BE MINIMUM OF 12" ABOVE WEATHER HEAD 3.) METER SOCKET TO BE MAXIMUM 6' 3" TO CENTERLINE ABOVE GRADE. 4.) METER BOARD TO BE TREATED FOR OUTDOOR APPLICATION AND MINMUM OF 3/4" THICK 5.) GROUND ROD SHOULD BE MINIMUM 6" APART 6.) METER BOARD TO BE SECURELY FASTERED TO POLE 7.) VERIFY POLE IS SET DEEP 8.) SCHEDULE 80 FROM SERVICE NEEDS TO BE SECURED 9.) 3' OF WORKING CLEARANE NECESSARY IN FRONT OF SERVICE 10.) DISCONNECT FOR MOBILE HOME REQUIRED WITHIN 30' OF HOME. |