Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL01045

Parcel: 12912030A


Addresses:

1021 E 27TH ST

Inspection Status: Denied

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
07/17/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*1.) 4 X 4 POLE DOES NOT MEET TEP REQUIREMENTS OF 17" MINIMUM CIRCUMERENCE AT POWER POLE. 2.) POLE TO BE MINIMUM OF 12" ABOVE WEATHER HEAD 3.) METER SOCKET TO BE MAXIMUM 6' 3" TO CENTERLINE ABOVE GRADE. 4.) METER BOARD TO BE TREATED FOR OUTDOOR APPLICATION AND MINMUM OF 3/4" THICK 5.) GROUND ROD SHOULD BE MINIMUM 6" APART 6.) METER BOARD TO BE SECURELY FASTERED TO POLE 7.) VERIFY POLE IS SET DEEP 8.) SCHEDULE 80 FROM SERVICE NEEDS TO BE SECURED 9.) 3' OF WORKING CLEARANE NECESSARY IN FRONT OF SERVICE 10.) DISCONNECT FOR MOBILE HOME REQUIRED WITHIN 30' OF HOME.