Permit: T01EL00962
Permit Details
Apply Date:
04/23/2001
Applicant:
FAHR JOHN H & ELIZABETH J JT/RS
Description:
UPGRADE:ELECTRIC FROM 100 TO 200 AMP
Outstanding Activity Conditions
Permit Number - T01EL00962
Permit Status: Closed
Permit Description: UPGRADE:ELECTRIC FROM 100 TO 200 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/23/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T01EL00962
Permite Description: UPGRADE:ELECTRIC FROM 100 TO 200 AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected | ||
| 05/03/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0245* 1) INSTALL SEALING LOCKNUT ON 1" CONNECTOR AT TOP OF BREAKER COMP. ALSO INSTALL BOND BUSHING 250-94 NEC. 2) 3/4" PENETRATION ABOVE BREAKER LINE ON SIDE OF PANEL MUST BE WATER TITE, REDUCING WASHERS WILL NOT BE APPROVED AS A RAIN TITE INSTALLATION 3) GROUND J BOX 370-47, 250 NEC |
Completed Inspections
Permit Status: Closed
Permit Number: T01EL00962
Permit Description: UPGRADE:ELECTRIC FROM 100 TO 200 AMP
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2001 | ELECTRIC - CABLE DROP | DSANTACR | Approved | IVRS - Inspection 0000* |