Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/03/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* 1) INSTALL SEALING LOCKNUT ON 1" CONNECTOR AT TOP OF BREAKER COMP. ALSO INSTALL BOND BUSHING 250-94 NEC. 2) 3/4" PENETRATION ABOVE BREAKER LINE ON SIDE OF PANEL MUST BE WATER TITE, REDUCING WASHERS WILL NOT BE APPROVED AS A RAIN TITE INSTALLATION 3) GROUND J BOX 370-47, 250 NEC |
| 04/25/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* CALL FOR FINAL WHEN NEW SERVICE IS TIED IN AND OLD IS DEMO'D |