Permit: T01CM05710
Permit Details
Status:
C of o
Type:
COMMERCIAL NEW
Address:
6444 E TANQUE VERDE RD
Address NEW:
6444 E TANQUE VERDE RD
Apply Date:
11/21/2001
Applicant:
N/A
Description:
NEW:BANK
Contractors:
- STEVENS LEINWEBER CONSTRUCTION I
Permit Reviews
Permit Number - T01CM05710
Permit Status: C of o
Permit Description: NEW:BANK
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/19/2002 | SITE | 05/25/2002 | COMPLETED |
| 06/21/2002 | REVISION | 07/09/2002 | COMPLETED |
| 11/21/2001 | 3RD PARTY REVIEW-COMMERCIAL | 04/12/2002 | COMPLETED |
| 11/21/2001 | SITE | 02/19/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01CM05710
Permit Status: C of o
Permit Description: NEW:BANK
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/21/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T01CM05710
Permit Description: NEW:BANK
Total Completed Inspections - 42
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2002 | ELECTRIC - UFER | DSANTACR | Approved | IVRS - Inspection 0000*NOTES ALSO U.G. SECONDARY STUB OUT OF BLDG. |
| 05/31/2002 | EXCAVATION/LAYOUT REBAR & ZON | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 06/07/2002 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK. 2.) AIR PRESSURE TEST FOR 2 1/2" WATER SERVICE ISOK 3.) OK TO BACKFILL TRENCH. 4.) NOTE: WILL REQUIRE A REVISED AND APPROVED DRAWING ON WASTE & VENT SYSTEM AND BLDG. DRAIN EXIT FROM BLDG. PRIOR TO NEXT INSPECTION. |
| 06/07/2002 | ELECTRIC - TEMPORARY POLE | DSANTACR | Approved | IVRS - Inspection 0000* |
| 06/20/2002 | STEM WALL/RETAINING WALL | AMATHIES | Approved | IVRS - Inspection 0000* |
| 07/31/2002 | PLUMBING - SEWER HCS CONNECT | TRINIVJR | Approved | 1.) SOIL WATER TEST IS OK 2.) HCS CONNECTION IS OK 3.) OK TO BACKFILL TRENCH. |
| 08/22/2002 | ROOF NAILING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 08/22/2002 | EXT METAL CLIPS/EXT SHEATHING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 09/16/2002 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection 0000*1.) Inspected fire damper openings o.k. to complete installation of dampers. 2.) Provide listing on attic insulation showing use in plenum rated ceiling. Cojmbustible material not allowed in return plenum. 3.) Checked fan coil for proper service access. is ok. 4.) Plans show duct smoke detectors installed in supply ducts. 2000 IMC requires they be installed in return ducts. |
| 09/17/2002 | PLUMBING - ABOVE CEILING | TRINIVJR | Approved | IVRS - Inspection 0000* |
| 09/25/2002 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection 0000* |
| 10/18/2002 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 10/29/2002 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection 0000* |
| 11/20/2002 | MECHANICAL - TEMP PWR FOR TEST | JMILITEL | Approved | IVRS - Inspection 0000* |
| 11/20/2002 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection 0000*WILL CHECK AIR HANDLER ON FINAL. OK FOR CEILING TILES. |
| 11/20/2002 | PLUMBING - TEMP POWER FOR TEST | TRINIVJR | Approved | |
| 11/20/2002 | PLUMBING - YARD WTR LINE/TEST | TRINIVJR | Approved | IVRS - Inspection 0000*1.) BACKFLOW PREVENTER HAS BEEN INSTALLED. |
| 11/20/2002 | BUILDING - TEMP POWER FOR TEST | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 11/20/2002 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 11/20/2002 | U VALUE FOR WINDOW | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 11/20/2002 | STUCCO MESH | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 11/20/2002 | FRAMING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 11/20/2002 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 11/20/2002 | BUILDING PRE-SLAB | AQUIROZ | Approved | |
| 11/22/2002 | ELECTRIC - TEMP POWER FOR TEST | DSANTACR | Approved | IVRS - Inspection 0000* |
| 11/22/2002 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | IVRS - Inspection 0000*ALL AREAS EXCEPT, ROOM #106. NOTES OK TEMP POWER FOR TEST UPON POSTING OF BOND. SUPT. & ELECTRICAL FOREMAN ONLY AUTHORIZED PERSONS WITH KEYS TO ELECTRIC ROOM. |
| 12/13/2002 | PLUMBING - INTERMEDIATE | TRINIVJR | Approved | IVRS - Inspection 0000*CLOSET RINGS HAVE BEEN SET. |
| 01/09/2003 | FIRE - FINAL | JEGAN | Approved | IVRS - Inspection 0000* |
| 01/09/2003 | PLUMBING - FINAL | JSTANLEY | Approved | IVRS - Inspection 0000*FINAL OK S.T.O.I NO GAS ON JOB. |
| 01/10/2003 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 01/10/2003 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 01/10/2003 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 01/10/2003 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 01/14/2003 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0000*OK FOR C OF O. |
| 01/14/2003 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | |
| 01/14/2003 | SIGN - FINAL | JYBARRA | Approved | |
| 01/22/2003 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection 0000* |
| 01/22/2003 | ELECTRIC - CABLE DROP | RHOLLAND | Approved | |
| 01/22/2003 | BUILDING - FINAL | RSUBA | Approved | IVRS - Inspection 0000* |
| 01/23/2003 | PERMIT FINALED | RSUBA | Approved | |
| 01/23/2003 | LANDSCAPE - FINAL | PGILBERT | Approved | |
| 01/23/2003 | ENGINEERING - FINAL | LMAKUS | Approved |