Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/23/2003 |
MECHANICAL - INTERMEDIATE |
|
Approved |
|
| 09/16/2002 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) Inspected fire damper openings o.k. to complete installation of dampers. 2.) Provide listing on attic insulation showing use in plenum rated ceiling. Cojmbustible material not allowed in return plenum. 3.) Checked fan coil for proper service access. is ok. 4.) Plans show duct smoke detectors installed in supply ducts. 2000 IMC requires they be installed in return ducts. |