Permit: T01CM05710

Parcel: 13316033E

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/23/2003 MECHANICAL - INTERMEDIATE Approved
09/16/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) Inspected fire damper openings o.k. to complete installation of dampers. 2.) Provide listing on attic insulation showing use in plenum rated ceiling. Cojmbustible material not allowed in return plenum. 3.) Checked fan coil for proper service access. is ok. 4.) Plans show duct smoke detectors installed in supply ducts. 2000 IMC requires they be installed in return ducts.