Permit Details

Status:
Closed
Type:
SINGLE FAMILY OTHER
Apply Date:
09/25/2001
Applicant:
N/A
Description:
GAS/AC
Contractors:
  • DEWOODY'S HEATING AND AIR CONDIT

Permit Reviews

Permit Number - T01CM04793
Permit Status: Closed
Permit Description: GAS/AC
Start Date Submittal Complete Date Status  
09/25/2001 RESIDENTIAL BLDG/ZONING 09/25/2001 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01CM04793
Permit Status: Closed
Permit Description: GAS/AC
Total Outstanding Activity Conditions - 1
Date Name
09/25/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T01CM04793
Permite Description: GAS/AC
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
01/22/2002 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection 0245*NOTES SEE WRITE UPS FOR 4640,4648.
11/20/2001 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0999*1.) LIQUIDTIGHT NON METALLIC FLEX NOT ALLOWED WHERE SUBJECT TO PHYSICAL DAMAGE (ON ROOF OUT IN OPEN ALSO NOT SUPPORTED 2.) UNIT CALLS FOR 25A MAX FUSE 3.) SLICED INSULATION BY TERMINATION 4.) DISCONNECT TO HAVE BUSHING OR CONNECTOR BETWEEN IT AN UNIT.

Completed Inspections

Permit Status: Closed
Permit Number: T01CM04793
Permit Description: GAS/AC
Total Completed Inspections - 2
Date Description Inspector Results Comments
11/20/2001 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection 0999*BLOCK & DAMP GAS PIPE ON ROOF. USE CONDUIT ON ELECTRICAL CIRCUIT PROVIDE A ROOF JACK AT ROOF PENETRATION. UNIT NOT FUSED CORRECTLY. PROVIDE A CONDENSATE DRAIN LINE RECALL FOR FINAL INSPECTION.
01/22/2002 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection 0000*

Documents

File Name Document Type  
None DOCUMENTS VIEW