Permit: T01CM04793

Parcel: 122121420

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/22/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
11/20/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) LIQUIDTIGHT NON METALLIC FLEX NOT ALLOWED WHERE SUBJECT TO PHYSICAL DAMAGE (ON ROOF OUT IN OPEN ALSO NOT SUPPORTED 2.) UNIT CALLS FOR 25A MAX FUSE 3.) SLICED INSULATION BY TERMINATION 4.) DISCONNECT TO HAVE BUSHING OR CONNECTOR BETWEEN IT AN UNIT.