Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/22/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* |
| 11/20/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) LIQUIDTIGHT NON METALLIC FLEX NOT ALLOWED WHERE SUBJECT TO PHYSICAL DAMAGE (ON ROOF OUT IN OPEN ALSO NOT SUPPORTED 2.) UNIT CALLS FOR 25A MAX FUSE 3.) SLICED INSULATION BY TERMINATION 4.) DISCONNECT TO HAVE BUSHING OR CONNECTOR BETWEEN IT AN UNIT. |