Permit Details

Status:
Final
Type:
MULTI FAMILY ALTERATION
Address NEW:
3632 E LEE ST #100
Apply Date:
09/18/2001
Applicant:
FAGIN, EDWARD A
Description:
INTERIOR REMODEL:APT
Contractors:
  • J W S CONSTRUCTION INC ,

Permit Reviews

Permit Number - T01CM04693
Permit Status: Final
Permit Description: INTERIOR REMODEL:APT
Start Date Submittal Complete Date Status  
09/18/2001 COMMERCIAL TI 03/25/2002 COMPLETED Review Details
09/20/2001 SITE 03/25/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01CM04693
Permit Status: Final
Permit Description: INTERIOR REMODEL:APT
Total Outstanding Activity Conditions - 1
Date Name
09/18/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T01CM04693
Permit Description: INTERIOR REMODEL:APT
Total Completed Inspections - 24
Date Description Inspector Results Comments
09/13/2002 PLUMBING - YARD WTR LINE/TEST TRINIVJR Approved 1.) SOIL WATER TEST FOR 4" BLDG. SEWER FROM HCS TO C.O. ONLY @ WEST SIDE OF BLDG. ONLY IS OK. 2.) NOTE: BLDG. SEWER REQUIRES (2) COMBOS FOR TWO WAY C.O. THE TWO WAY FITTING IS NOT ACCEPTED WITH A EXTENTION. 3.) OK TO BACKFILL TRENCH WEST SIDE ONLY. 4.) NOTE: WILL REQUIRE A REVISED AND APPROVED DRAWING ON SITE SEWER & WATER PRIOR TO FINAL INSPECTION.
09/16/2002 PLUMBING - SEWER HCS CONNECT TRINIVJR Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK.
2.) HCS CONNECTION IS OK 3.) YARD WATER LINES FROM METER LOCATION TO BLDG. SERVICE IS OK 4.) OK TO BACKFILL TRENCH.
11/04/2002 FRAMING AMATHIES Approved IVRS - Inspection 0000*
11/05/2002 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection 0000*WATER TEST DOWN. TEST ON WAST VENT & WATER OK SUBJECT TO APPROVED REVISED PLAN BY NEXT INSP. ON LOCATION OF WATER LINES & SITE SEWER/RED LINES ON JOB AT THIS TIME.
11/14/2002 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection 0000*OK UNITS 4 & 5.
11/15/2002 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection 0000*
HAVE ENGINEER ADDRESS DUCT WORK INSULATION EXISTING INSUL. WAS 1/2" DUCT WRAP, ACCEPTABLE AT TIME BLDG WAS BUILT. EXISTING INSULATION. HAS BEEN DISTURBED BY LARGE NEW ELECT. FEEDER WIRES BEING PULLED INTO SOFFITTS ABOVE DUCTWORK. ENGINEER SHOULD ADDRESS THIS ISSUE.
01/09/2003 PLUMBING - GAS PRESSURE TEST JSTANLEY Approved IVRS - Inspection 0000*TEST ONLY OK.
01/24/2003 ELECTRIC - CABLE DROP RHOLLAND Approved IVRS - Inspection 0000*SENT TO TEP ON 1/27/03 AT 9:15AM OK CABLE DROP ONLY. 1.) A GAS AND WATER BOND ARE NEEDED.
02/03/2003 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection 0000*
02/03/2003 MECHANICAL - ABOVE CEILING CWILLIAM Approved
02/10/2003 SIGN - FINAL JYBARRA Approved IVRS - Inspection 0000*
02/10/2003 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection 0000*OK FINAL
02/10/2003 ELECTRIC - TEMPORARY SERVICE RHOLLAND Approved
02/10/2003 ELECTRIC - ABOVE CEILING RHOLLAND Approved
02/10/2003 ELECTRIC - UNDERGROUND RHOLLAND Approved
02/11/2003 ELECTRIC - UFER RHOLLAND Approved
02/19/2003 PLUMBING - FINAL JSTANLEY Approved IVRS - Inspection 0000*LAST INSP PROVIDE GAS CARD.
02/20/2003 PERMIT FINALED AQUIROZ Approved
02/20/2003 ENGINEERING - FINAL JBRUCKME Approved
02/20/2003 FIRE - FINAL JEGAN Approved IVRS - Inspection 0000*
02/20/2003 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection 0000*OK C OF O
02/20/2003 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection 0000*
02/20/2003 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection 0000*
02/28/2003 RIGHT OF WAY - FINAL MOTERO Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW