Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2003 |
PLUMBING - INTERMEDIATE |
|
Approved |
|
| 11/05/2002 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*WATER TEST DOWN. TEST ON WAST VENT & WATER OK SUBJECT TO APPROVED REVISED PLAN BY NEXT INSP. ON LOCATION OF WATER LINES & SITE SEWER/RED LINES ON JOB AT THIS TIME. |
| 09/30/2002 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*PENDING REVISION. |
| 09/26/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*WATER TEST WAS DOWN. |
| 09/24/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) MUST PROVIDE WATER TEST WITH A 10' HEAD. 2.) VENT AGGREGATE CROSS SECTIONAL AREA MUST EQUAL THE LARGEST REQUIRED BLDG. SEWER SEE SECTION 904.1 94 UPC. 3.) RETEST SYSTEM. |