Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T01CM03309
Permit Details
Status:
C of o
Type:
COMMERCIAL NEW
Address:
3231 N CRAYCROFT RD BLDG #04
Address NEW:
3231 N CRAYCROFT RD BLDG #04
Apply Date:
07/03/2001
Applicant:
OSBORNE DIANA
Description:
NEW SCIENCE COMPLEX
Permit Reviews
Permit Number - T01CM03309
Permit Status: C of o
Permit Description: NEW SCIENCE COMPLEX
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/17/2002 | REVISION | 01/28/2002 | COMPLETED |
| 02/19/2002 | REVISION | 03/26/2002 | COMPLETED |
| 05/21/2002 | REVISION | 06/12/2002 | COMPLETED |
| 06/13/2002 | REVISION | 06/21/2002 | COMPLETED |
| 07/03/2001 | 3RD PARTY REVIEW-COMMERCIAL | 09/19/2001 | COMPLETED |
| 09/19/2001 | RESUBMITTAL | 09/20/2001 | COMPLETED |
Completed Inspections
Permit Status: C of o
Permit Number: T01CM03309
Permit Description: NEW SCIENCE COMPLEX
Total Completed Inspections - 35
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2001 | EXCAVATION/LAYOUT REBAR & ZON | AMATHIES | Approved | IVRS - Inspection 0000* |
| 11/29/2001 | PLUMBING - INTERMEDIATE | TRINIVJR | Approved | IVRS - Inspection 0000*1.) AIR TEST FOR 2" WATER SERVICE UNDER SLAB IS OK. |
| 11/30/2001 | ELECTRIC - UFER | DSANTACR | Approved | IVRS - Inspection 0000* |
| 11/30/2001 | STEM WALL/RETAINING WALL | AMATHIES | Approved | IVRS - Inspection 0000* |
| 12/03/2001 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection 0000*INSPECTION ON UNDERGROUND REFER LINES BLDG.4 NORTHWEST OK TO COVER. |
| 12/11/2001 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection 0000* |
| 12/11/2001 | BUILDING PRE-SLAB | AMATHIES | Approved | IVRS - Inspection 0000* |
| 12/17/2001 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection 0000*1.) 1/2" CSST FROM LAB STATIONS TO MAINFOLD OK CONTRACTOR STILL NEEDS TO RUN PVC VENT TO OUTSIDE WILL CALL FOR THIS INSPECTION 2.) OK TO COVER CSST PENDING REVISED APPROVED PLAN. |
| 12/19/2001 | PLUMBING - YARD WTR LINE/TEST | TRINIVJR | Approved | IVRS - Inspection 0000*1.) AIR PRESSURE TEST 60LB FOR 2" U.G. WATER IN MECH. RM #121 IS OK AND IS STUBBED OUT OF BLDG. ONLY. |
| 01/23/2002 | FRAMING | AMATHIES | Approved | IVRS - Inspection 0000* |
| 01/23/2002 | EXT METAL CLIPS/EXT SHEATHING | AMATHIES | Approved | IVRS - Inspection 0000* |
| 01/30/2002 | ROOF NAILING | AMATHIES | Approved | IVRS - Inspection 0000* |
| 03/11/2002 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection 0000* |
| 03/19/2002 | STUCCO MESH | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 06/04/2002 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 07/12/2002 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 07/18/2002 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0000*1.) SEAL EXHAUST DUCTS ON FUME HOODS. 2.) PROVIDE SUPPORT ON EXHAUST DUCT ON ROOF 3.) INSTALL CANVAS CONNECTORS COVERS ON EXHAUST DUCT ON ROOF. OK FOR TEMP C OF O. |
| 07/18/2002 | ELECTRIC - ABOVE CEILING | MCAPISTR | Approved | IVRS - Inspection 0000* |
| 08/05/2002 | FIRE - FINAL | LTHOMAS | Approved | |
| 08/12/2002 | PLUMBING - FINAL | TRINIVJR | Approved | IVRS - Inspection 0000*1.) PLBG FINAL IS OK 2.) OK FOR C OF O. |
| 08/12/2002 | PLUMBING - SEWER HCS CONNECT | TRINIVJR | Approved | |
| 08/12/2002 | PLUMBING - GAS PRESSURE TEST | TRINIVJR | Approved | |
| 08/26/2002 | LANDSCAPE - FINAL | PGILBERT | Approved | |
| 08/27/2002 | FIRE - ALARM FINAL | LTHOMAS | Approved | |
| 08/29/2002 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 08/29/2002 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 08/29/2002 | U VALUE FOR WINDOW | AQUIROZ | Approved | IVRS - Inspection 0000* |
| 08/30/2002 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | |
| 08/30/2002 | ENGINEERING - FINAL | JBRUCKME | Approved | |
| 08/30/2002 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 08/30/2002 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 08/30/2002 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 08/30/2002 | ELECTRIC - FINAL | MCAPISTR | Approved | IVRS - Inspection 0000* |
| 08/30/2002 | ELECTRIC - CABLE DROP | MCAPISTR | Approved | |
| 09/25/2002 | PERMIT FINALED | SLONG | Approved |