Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T01CM03309

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/30/2002 MECHANICAL - ABOVE CEILING Approved
06/04/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) NEED TO SEE PAPERWORK ON DELETED FIRE SMOKE DAMPERS. 2.) PROVIDE LISTING & INSTALL INSTRUCTIONS FOR ROUND FIRE/SMOKE DAMPER REMOVE METAL PLATE. OK FOR CEILING TILES.
03/11/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*INSPECTED HANGER RODS ABOVE CEILING OK FOR SHEET ROCK. ANCHOR REFER LINE INSIDE WALL. ISOLATE COPPER FROM STEEL UNISTRUT CLAMPS.
02/05/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*INSPECTION ON DUCT ABOVE RESTROOM IN BLDG 4 OK TO COVER.